NSN: 5925-00-700-8349
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Case Material
plastic
-
Thread Series Designator
uns
-
Nominal Thread Size
0.469 inches
-
Body Width
0.750 inches maximum
-
Terminal Type And Quantity
2 tab w/screw
-
Inclosure Protection Type For Which Designed
vibration resistant and shock resistant and explosion proof
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
138.0 single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac single location and 6000.0 dc single location
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac single location and 30.0 dc single location
-
Bushing Length
0.235 inches minimum and 0.250 inches maximum
-
Mounting Surface To Terminal End Distance
1.843 inches maximum
-
Body Style
single pole type
-
Frequency In Hertz
400.0 single location
-
Precious Material And Location
contact surfaces silver
-
Maximum Continuous Load Current Rating Per Pole
2.0 amperes ac single location and 2.0 amperes dc single location
-
Main Contact Tripping Mechanism Type
trip free
-
Trip Release Characteristic
time delay single location
-
Internal Trip Release Configuration
series trip single location
-
Pole Quantity
1
-
Manual Actuator Type And Quantity
1 push-pull
-
Trip Release Method
thermal single location
-
Center To Center Distance Between Terminals Parallel To Length
0.669 inches minimum and 0.731 inches maximum
-
Circuit Protection Type
overcurrent single location
-
Thread Quantity Per Inch
32
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.400 minimum at 200 pct single location and 3.000 maximum at 200 pct single location
-
Cubic Measure
2.255 cubic inches
-
Unpackaged Unit Weight
0.100 pounds
-
Actuator Function
trip-reset
-
Storage Type
general purpose warehouse
-
Precious Material
silver
-
Actuator Position Designation
at pole one
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Body Length
1.187 inches maximum
-
Trip Release Ambient Temp Rating
25.0 deg celsius maximum single location
-
Reset Method
manual
-
Fragility Factor
moderately rugged