Technical Characteristics
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac single location and 15.0 amperes dc single location
-
Mounting Surface To Terminal End Distance
2.340 inches minimum and 2.400 inches maximum
-
Frequency In Hertz
400.0 single location
-
Body Style
single pole type
-
Bushing Length
0.235 inches minimum and 0.250 inches maximum
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac single location and 30.0 dc single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
138.0 single location
-
Auxiliary Switch Function And Quantity
1 alarm
-
Body Width
0.750 inches maximum
-
Case Material
plastic
-
Circuit Protection Type
overcurrent single location
-
Inclosure Protection Type For Which Designed
shockproof and corrosion resistant and explosion proof and vibration resistant and arc resistant
-
Trip Release Method
thermal single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
6000.0 ac single location and 6000.0 dc single location
-
Manual Actuator Type And Quantity
1 push-pull
-
Center To Center Distance Between Terminals Parallel To Length
1.160 inches minimum and 1.220 inches maximum
-
Switch Contact Arrangement
single pole, double throw
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.800 inches minimum and 1.820 inches maximum
-
Unpackaged Unit Weight
3.250 ounces
-
Actuator Function
reset
-
Thread Series Designator
unc
-
Reset Method
manual
-
Actuator Position Designation
at pole one
-
Terminal Type And Quantity
2 screw
-
Mounting Facility Type And Quantity
2 threaded hole
-
Thread Quantity Per Inch
32
-
Pole Quantity
1
-
Body Length
2.189 inches maximum
-
Internal Trip Release Configuration
series trip single location
-
Nominal Thread Size
0.138 inches
-
Trip Release Characteristic
time delay single location
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal single location
-
Main Contact Tripping Mechanism Type
trip free
-
Trip Delay Time In Seconds Per Rated Continuous Current
18.000 minimum at 200 pct single location and 47.000 maximum at 200 pct single location