NSN: 5925-00-729-7568
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Overall Width
0.750 inches nominal
-
Case Material
plastic
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.062 inches nominal
-
Arc Quenching Method
magnetic blowout
-
Mounting Facility Type And Quantity
2 threaded hole
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
0.5 amperes ac
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
2000.0 ac
-
Trip Release Method
magnetic
-
Nominal Thread Size
0.138 inches
-
Inclosure Protection Type For Which Designed
explosion proof and fungus resistant
-
Frequency In Hertz
60.0
-
Terminal Type And Quantity
2 threaded stud
-
Trip Delay Time In Seconds Per Rated Continuous Current
16.000 minimum at 125 pct and 70.000 maximum at 125 pct and 3.000 minimum at 200 pct and 8.500 maximum at 200 pct and 1.000 minimum at 300 pct and 3.500 maximum at 300 pct
-
Precious Material
silver
-
Thread Series Designator
unc
-
Overall Length
2.500 inches nominal
-
Overall Height
3.172 inches nominal
-
Pole Quantity
1
-
Operating Voltage Type And Rating Per Pole In Volts
208.0 ac
-
Circuit Protection Type
overcurrent
-
Trip Release Characteristic
time delay
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Function
reset