NSN: 5925-00-733-7810

Circuit Breakers

CIRCUIT BREAKER

5925 - Circuit Breakers

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Body Style

    2a single pole type

  • Body Width

    0.625 inches maximum

  • Case Material

    metal

  • Center To Center Distance Between Terminals Parallel To Length

    0.906 inches maximum

  • Test Data Document

    81349-mil-c-39019 specification

  • Frequency In Hertz

    60.0

  • Inclosure Protection Type For Which Designed

    fungus resistant and hermetically sealed

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.055 minimum at 200 pct and 0.950 maximum at 200 pct and 0.240 maximum at 400 pct single location

  • Actuator Position Designation

    at pole one

  • Actuator Function

    trip-reset

  • Manual Actuator Type And Quantity

    1 toggle

  • Main Contact Tripping Mechanism Type

    trip free

  • Reset Method

    manual

  • Ultimate Trip Time Per Pole In Seconds

    0.200 minimum and 7.000 maximum single location

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0

  • Circuit Protection Type

    overcurrent single location

  • Thread Quantity Per Inch

    32

  • Mounting Facility Type And Quantity

    1 threaded bushing

  • Pole Quantity

    1

  • Mounting Surface To Terminal End Distance

    1.700 inches maximum

  • Body Length

    1.562 inches maximum

  • Bushing Length

    0.380 inches maximum

  • Terminal Type And Quantity

    2 wire hook

  • Thread Series Designator

    unef

  • Nominal Thread Size

    0.375 inches

  • Internal Trip Release Configuration

    series trip single location

  • Trip Release Characteristic

    time delay single location

  • Trip Release Method

    magnetic single location

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    300.0 ac single location

  • Operating Voltage Type And Rating Per Pole In Volts

    240.0 ac single location

  • Maximum Continuous Load Current Rating Per Pole

    500.0 milliamperes ac single location

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...