NSN: 5925-00-752-4017
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Overall Height
3.422 inches nominal
-
Overall Width
2.250 inches nominal
-
Pole Quantity
3
-
Mounting Facility Type And Quantity
6 threaded hole
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
3.0 amperes ac
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac
-
Circuit Protection Type
overcurrent
-
Trip Release Characteristic
time delay
-
Nominal Thread Size
0.138 inches
-
Frequency In Hertz
400.0
-
Precious Material
silver
-
Overall Length
2.500 inches nominal
-
Case Material
plastic
-
Arc Quenching Method
magnetic blowout
-
Operating Voltage Type And Rating Per Pole In Volts
200.0 ac
-
Trip Release Method
magnetic
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Function
reset
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.600 nominal at 125 pct and 0.200 nominal at 200 pct
-
Inclosure Protection Type For Which Designed
watertight and dustproof and fungus resistant and moisture resistant
-
Thread Series Designator
unc
-
Terminal Type And Quantity
6 threaded stud