Technical Characteristics
-
Test Data Document
81349-mil-c-13516 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type
-
~1
data on certain environmental and performanc
-
Maximum Continuous Load Current Rating Per Pole
50.0 amperes ac single location and 50.0 amperes dc single location
-
Body Style
rectangular dimensional envelope
-
Thread Series Designator
unc
-
Nominal Thread Size
0.190 inches
-
Trip Release Ambient Temp Rating
25.0 deg celsius maximum single location
-
Mounting Facility Type And Quantity
2 threaded hole
-
Thread Quantity Per Inch
32
-
Circuit Protection Type
overcurrent single location
-
Trip Release Method
thermal single location
-
Pole Quantity
1
-
Overall Height
1.406 inches nominal
-
Inclosure Protection Type For Which Designed
watertight
-
Internal Trip Release Configuration
series trip single location
-
Trip Release Characteristic
time delay single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1200.0 ac single location and 1200.0 dc single location
-
Operating Voltage Type And Rating Per Pole In Volts
30.0 ac single location and 30.0 dc single location
-
Trip Delay Time In Seconds Per Rated Continuous Current
3600.000 nominal at 125 pct single location and 30.000 nominal at 200 pct single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
115.0 single location
-
Frequency In Hertz
60.0 single location
-
Overall Width
1.875 inches nominal
-
Reset Method
automatic
-
Overall Length
3.156 inches nominal
-
Case Material
plastic
-
Terminal Type And Quantity
2 threaded stud