NSN: 5925-00-783-6221
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Trip Delay Time In Seconds Per Rated Continuous Current
14.000 minimum at 300 pct all locations and 47.000 minimum at 200 pct all locations and 110.000 maximum at 200 pct all locations and 29.000 maximum at 300 pct all locations
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Reset Method
manual
-
Actuator Function
trip-reset
-
Maximum Continuous Load Current Rating Per Pole
90.0 amperes ac all locations and 90.0 amperes dc all locations
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Operating Voltage Type And Rating Per Pole In Volts
600.0 ac all locations and 250.0 dc all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Trip Release Method
thermal-magnetic all locations
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
-
Manual Actuator Type And Quantity
1 toggle
-
Frequency In Hertz
60.0 all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
10000.0 ac all locations and 10000.0 dc all locations
-
Terminal Type And Quantity
6 screw
-
Case Material
plastic