NSN: 5925-00-800-1481
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Trip Delay Time In Seconds Per Rated Continuous Current
10.000 minimum at 300 pct all locations and 28.000 maximum at 300 pct all locations and 6.000 minimum at 400 pct all locations and 30.000 minimum at 200 pct all locations and 102.000 maximum at 200 pct all locations and 14.000 maximum at 400 pct all
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip all locations
-
Ultimate Trip Time Per Pole In Seconds
90.000 minimum all locations and 540.000 maximum all locations
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Operating Voltage Type And Rating Per Pole In Volts
600.0 ac all locations and 250.0 dc all locations
-
Mounting Facility Type And Quantity
4 threaded hole
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 all locations
-
Manual Actuator Type And Quantity
1 toggle
-
Terminal Type And Quantity
6 quick disconnect, female
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
100000.0 ac all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Maximum Continuous Load Current Rating Per Pole
40.0 amperes ac all locations and 40.0 amperes dc all locations
-
Nominal Thread Size
0.250 inches
-
Case Material
plastic
-
Trip Release Method
thermal all locations
-
~1
locations