NSN: 5925-00-817-4491
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Pole Quantity
1
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
50.0 amperes ac single location and 50.0 amperes dc
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
3500.0 ac single location and 6000.0 dc
-
Circuit Protection Type
overcurrent single location
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 push-pull
-
Actuator Function
reset
-
Nominal Thread Size
0.468 inches
-
Overall Width
0.687 inches nominal
-
Case Material
plastic
-
Arc Quenching Method
air
-
Trip Release Method
magnetic single location
-
Trip Release Characteristic
time delay single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
138.0 single location
-
Trip Delay Time In Seconds Per Rated Continuous Current
15.000 minimum at 200 pct single location and 55.000 maximum at 200 pct and 2.000 minimum at 400 pct and 7.000 maximum at 400 pct
-
Inclosure Protection Type For Which Designed
explosion proof
-
Thread Series Designator
uns
-
Terminal Type And Quantity
2 screw
-
Overall Length
1.093 inches nominal
-
Overall Height
2.500 inches nominal
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal single location