NSN: 5925-00-826-6901
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Length
5.240 inches minimum and 5.260 inches maximum
-
Body Width
2.990 inches minimum and 3.010 inches maximum
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac all locations
-
Center To Center Distance Between Terminals Parallel To Length
4.349 inches minimum and 4.369 inches maximum
-
Main Contact Tripping Mechanism Type
trip free
-
Internal Trip Release Configuration
series trip third location
-
Frequency In Hertz
60.0 all locations
-
Manual Actuator Type And Quantity
1 toggle
-
Internal Trip Release Configuration
series trip second location
-
Body Style
multipole-single actuator type
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Trip Delay Time In Seconds Per Rated Continuous Current
70000.000 nominal at 200 pct all locations and 20000.000 nominal at 300 pct all locations
-
Actuator Position Designation
at pole two
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Trip Release Method
magnetic all locations
-
Terminal Type And Quantity
6 threaded stud and 2 wire lead
-
Arc Quenching Method
air
-
Thread Quantity Per Inch
32
-
Ultimate Trip Time Per Pole In Seconds
10000.000 nominal all locations
-
Body Height
2.677 inches minimum and 2.697 inches maximum
-
Boss Height
0.209 inches minimum and 0.229 inches maximum
-
Mounting Facility Type And Quantity
4 threaded hole
-
Actuator Function
trip-reset
-
Trip Release Characteristic
time delay all locations
-
Storage Type
general purpose warehouse
-
Thread Series Designator
unf
-
Reset Method
manual
-
Nominal Thread Size
0.190 inches
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.302 inches minimum and 2.322 inches maximum
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
3
-
Fragility Factor
moderately rugged
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.974 inches minimum and 0.994 inches maximum
-
Case Material
plastic
-
Internal Trip Release Configuration
relay trip first location
-
Center To Center Distance Between Terminals Parallel To Width
0.974 inches minimum and 0.994 inches maximum