Technical Characteristics
-
Trip Release Method
magnetic single location
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac single location
-
Overall Height
5.343 inches nominal
-
Overall Length
3.265 inches nominal
-
Terminal Type And Quantity
2 screw
-
Circuit Protection Type
overcurrent single location
-
Ultimate Trip Time Per Pole In Seconds
80.000 minimum single location and 400.000 maximum single location
-
Pole Quantity
1
-
Manual Actuator Type And Quantity
1 toggle
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac single location
-
Unthreaded Mounting Hole Diameter
0.164 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Main Contact Tripping Mechanism Type
trip free
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes ac single location
-
Special Features
mounting hole/stud quanity 1
-
Frequency In Hertz
60.0 single location
-
Overall Width
1.025 inches nominal
-
Trip Release Characteristic
instantaneous single location and time delay single location
-
Reset Method
automatic
-
Case Material
plastic
-
Trip Delay Time In Seconds Per Rated Continuous Current
19.000 minimum at 200 pct single location and 80.000 minimum at 125 pct single location and 400.000 maximum at 125 pct single location and 60.000 maximum at 200 pct single location and 6.000 minimum at 300 pct single location and 9.000 maximum at 300 pct
-