NSN: 5925-00-865-9618
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Arc Quenching Method
magnetic blowout
-
Inclosure Protection Type For Which Designed
general purpose
-
Body Style
single pole type
-
Frequency In Hertz
60.0 single location
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes ac single location and 20.0 amperes dc single location
-
Terminal Type And Quantity
2 compression
-
Trip Release Characteristic
instantaneous single location and time delay single location
-
Trip Delay Time In Seconds Per Rated Continuous Current
24.000 minimum at 200 pct single location and 65.000 maximum at 200 pct single location
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
5.219 inches nominal
-
Boss Height
0.203 inches nominal
-
Body Height
3.406 inches nominal
-
Case Material
plastic
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
140.0 single location
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.125 inches nominal
-
Mounting Facility Type And Quantity
4 slot
-
Reset Method
manual
-
Actuator Position Designation
at pole one
-
Mounting Slot Width
0.250 inches nominal
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Trip Release Ambient Temp Rating
40.0 deg celsius nominal single location
-
Operating Voltage Type And Rating Per Pole In Volts
277.0 ac single location and 125.0 dc single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
14000.0 ac single location and 10000.0 dc single location
-
Circuit Protection Type
overcurrent single location
-
Body Length
6.219 inches nominal
-
Body Width
1.375 inches nominal
-
Pole Quantity
1
-
Center To Center Distance Between Terminals Parallel To Length
5.125 inches nominal
-
Manual Actuator Type And Quantity
1 toggle
-
Trip Release Method
thermal-magnetic single location
-
Main Contact Tripping Mechanism Type
trip free