NSN: 5925-00-866-3106
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 nominal at 200 pct single location and 0.100 nominal at 325 pct single location
-
Terminal Type And Quantity
2 screw
-
Bushing Length
0.290 inches nominal
-
Thread Quantity Per Inch
32
-
Circuit Protection Type
overcurrent single location
-
Body Length
1.750 inches nominal
-
Manual Actuator Type And Quantity
1 push-pull
-
Switch Voltage Rating And Type In Volts
130.0 ac and 28.0 dc
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
135.0 single location
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Pole Quantity
1
-
Case Material
metal
-
Internal Trip Release Configuration
series trip single location
-
Switch Location And Position Designation
external at pole one
-
Trip Release Characteristic
time delay single location
-
Main Contact Tripping Mechanism Type
trip free
-
Switch Contact Arrangement
single pole, single throw, normally closed
-
Switch Current Rating And Type In Amps
7.0 ac and 7.0 dc
-
Body Style
single pole type
-
Auxiliary Switch Function And Quantity
1 alarm
-
Operating Voltage Type And Rating Per Pole In Volts
32.0 dc single location
-
Nominal Thread Size
0.469 inches
-
Thread Series Designator
uns
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Actuator Position Designation
at pole one
-
Center To Center Distance Between Terminals Parallel To Length
1.341 inches nominal
-
Mounting Surface To Terminal End Distance
1.638 inches nominal
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Trip Release Method
magnetic single location
-
Switch Terminal Type
tab, solder lug
-
Maximum Continuous Load Current Rating Per Pole
2.0 amperes dc single location
-
Body Width
0.625 inches nominal
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac single location
-
Reset Method
manual