NSN: 5925-00-878-6034
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.500 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
22.000 minimum at 200 pct all locations and 80.000 maximum at 200 pct all locations
-
Mounting Surface To Terminal End Distance
2.359 inches nominal
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Length
1.938 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.062 inches nominal
-
Terminal Type And Quantity
6 threaded stud
-
Center To Center Distance Between Terminals Parallel To Width
1.500 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
110.0 all locations
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Internal Trip Release Configuration
series trip all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Thread Quantity Per Inch
32
-
Trip Release Method
magnetic-hydraulic all locations
-
Body Style
multipole-multiple actuator type
-
Inclosure Protection Type For Which Designed
moisture resistant and fungus resistant and explosion proof
-
Unpackaged Unit Weight
14.000 ounces
-
Mounting Facility Type And Quantity
6 threaded hole
-
Nominal Thread Size
0.138 inches
-
Body Width
2.250 inches nominal
-
Main Contact Tripping Mechanism Type
trip free
-
Arc Quenching Method
magnetic blowout
-
Body Length
2.500 inches nominal
-
Boss Height
0.125 inches nominal
-
Frequency In Hertz
400.0 all locations
-
Maximum Continuous Load Current Rating Per Pole
4.1 amperes ac all locations
-
Manual Actuator Type And Quantity
3 toggle
-
Operating Voltage Type And Rating Per Pole In Volts
208.0 ac all locations
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Reset Method