NSN: 5925-00-883-6011
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Boss Height
0.130 inches minimum and 0.150 inches maximum
-
Case Material
plastic
-
Terminal Type And Quantity
6 threaded stud
-
Center To Center Distance Between Terminals Parallel To Width
0.750 inches minimum and 0.770 inches maximum
-
Fragility Factor
moderately rugged
-
Switch Terminal Type
tab, solder lug
-
Special Handling Feature
magnetic
-
Pole Quantity
3
-
Manual Actuator Type And Quantity
3 toggle
-
Body Length
2.500 inches minimum and 2.530 inches maximum
-
Switch Contact Arrangement
single pole, double throw
-
Unpackaged Unit Weight
0.875 pounds
-
Switch Current Rating And Type In Amps
2.5 ac and 1.0 dc
-
Switch Voltage Rating And Type In Volts
250.0 ac and 50.0 dc
-
Mounting Facility Type And Quantity
6 threaded hole
-
Center To Center Distance Between Terminals Parallel To Length
1.930 inches minimum and 1.950 inches maximum
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 all locations
-
Nominal Thread Size
0.138 inches
-
Main Contact Tripping Mechanism Type
trip free
-
Inclosure Protection Type For Which Designed
general purpose
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.740 inches minimum and 0.760 inches maximum
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 minimum at 200 pct all locations and 10.000 maximum at 200 pct all locations
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations
-
Frequency In Hertz
400.0 all locations
-
Body Width
2.270 inches minimum and 2.290 inches maximum
-
Mounting Surface To Terminal End Distance
2.318 inches minimum and 2.462 inches maximum
-
Auxiliary Switch Function And Quantity
1 alarm
-
Circuit Protection Type
overcurrent all locations
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Switch Location And Position Designation
internal at pole three
-
Storage Type
general purpose warehouse
-
Maximum Continuous Load Current Rating Per Pole
1.5 amperes ac all locations
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Internal Trip Release Configuration
series trip all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.050 inches minimum and 2.070 inches maximum
-
Thread Quantity Per Inch
32
-
Trip Release Method
magnetic all locations
-
Body Style
multipole-multiple actuator type