NSN: 5925-00-897-9481
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Case Material
plastic
-
Thread Series Designator
unc
-
Terminal Type And Quantity
6 threaded stud
-
Center To Center Distance Between Terminals Parallel To Width
0.735 inches minimum and 0.765 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.047 inches minimum and 2.077 inches maximum
-
Switch Contact Arrangement
single pole,double throw
-
Fragility Factor
moderately rugged
-
Pole Quantity
3
-
Arc Quenching Method
magnetic blowout
-
Storage Type
general purpose warehouse
-
Thread Quantity Per Inch
32
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac
-
Trip Release Method
magnetic
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Auxiliary Switch Function And Quantity
1 alarm
-
Internal Trip Release Configuration
series trip
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.500 minimum at 200 pct and 1.200 maximum at 200 pct
-
Body Width
2.299 inches minimum and 2.301 inches maximum
-
Center To Center Distance Between Terminals Parallel To Length
1.928 inches minimum and 1.948 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.735 inches minimum and 0.765 inches maximum
-
Boss Height
0.130 inches minimum and 0.150 inches maximum
-
Mounting Surface To Terminal End Distance
2.409 inches minimum and 2.533 inches maximum
-
Mounting Facility Type And Quantity
6 threaded hole
-
Special Handling Feature
magnetic
-
Maximum Continuous Load Current Rating Per Pole
750.0 milliamperes ac
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac
-
Circuit Protection Type
overcurrent
-
Trip Release Characteristic
time delay
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0
-
Manual Actuator Type And Quantity
3 toggle
-
Actuator Function
trip-reset
-
Actuator Position Designation
at each pole
-
External Actuator Linkage Arrangement
one,two,and three linked
-
Nominal Thread Size
0.138 inches
-
Switch Location And Position Designation
internal at pole one
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant and shock resistant and humidity resistant and salt spray proof
-
Switch Current Rating And Type In Amps
2.5 ac and 1.0 dc
-
Switch Voltage Rating And Type In Volts
250.0 ac and 50.0 dc
-
Frequency In Hertz
400.0
-
Test Data Document
13499-260-4015 drawing
-
Body Style
multipole-multiple actuator type
-
Body Length
2.485 inches minimum and 2.515 inches maximum
-
Switch Terminal Type
tab,solder lug
-
Unpackaged Unit Weight
14.250 ounces