NSN: 5925-00-902-0305

Circuit Breakers

CIRCUIT BREAKER

5925 - Circuit Breakers

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Fragility Factor

    moderately rugged

  • Special Handling Feature

    magnetic

  • Thread Series Designator

    unc

  • Reset Method

    manual

  • Actuator Position Designation

    at pole one

  • Body Length

    3.719 inches nominal

  • Storage Type

    general purpose warehouse

  • Actuator Function

    trip-reset

  • Mounting Facility Type And Quantity

    2 threaded hole

  • Thread Quantity Per Inch

    32

  • Circuit Protection Type

    overcurrent single location

  • Body Width

    0.990 inches nominal

  • Trip Delay Time In Seconds Per Rated Continuous Current

    20.000 minimum at 200 pct single location and 100.000 maximum at 200 pct single location

  • Mounting Surface To Terminal End Distance

    2.177 inches minimum and 3.301 inches maximum

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    4000.0 dc single location

  • Case Material

    plastic

  • Terminal Type And Quantity

    2 threaded stud

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.750 inches nominal

  • Inclosure Protection Type For Which Designed

    fungus resistant and explosion resistant and moisture resistant and shock resistant and vibration resistant

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    150.0 single location

  • Trip Release Method

    magnetic-hydraulic single location

  • Body Style

    single pole type

  • Operating Voltage Type And Rating Per Pole In Volts

    50.0 dc single location

  • Maximum Continuous Load Current Rating Per Pole

    50.0 amperes dc single location

  • Arc Quenching Method

    magnetic blowout

  • Main Contact Tripping Mechanism Type

    trip free

  • Trip Release Characteristic

    time delay single location

  • Boss Height

    0.156 inches nominal

  • Nominal Thread Size

    0.138 inches

  • Internal Trip Release Configuration

    series trip single location

  • Manual Actuator Type And Quantity

    1 toggle

  • Unpackaged Unit Weight

    0.690 pounds

  • Pole Quantity

    1

  • Center To Center Distance Between Terminals Parallel To Length

    3.063 inches nominal

Related Manufacturers

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...