Technical Characteristics

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac single location

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    5000.0 ac single location

  • Circuit Protection Type

    overcurrent single location

  • Ultimate Trip Time Per Pole In Seconds

    1.500 minimum and 6.500 maximum single location

  • Main Contact Tripping Mechanism Type

    trip free

  • Manual Actuator Type And Quantity

    1 toggle

  • Actuator Position Designation

    at pole one

  • Terminal Type And Quantity

    2 compression

  • Body Style

    9a single pole type

  • Body Length

    5.250 inches nominal

  • Body Width

    1.500 inches nominal

  • Body Height

    2.687 inches nominal

  • Unthreaded Mounting Hole Diameter

    0.190 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    4.359 inches nominal

  • Boss Height

    0.218 inches nominal

  • Pole Quantity

    1

  • Mounting Facility Type And Quantity

    4 unthreaded hole

  • Trip Release Method

    magnetic-hydraulic single location

  • Trip Release Characteristic

    time delay single location

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 single location

  • Reset Method

    manual

  • Actuator Function

    trip-reset

  • Internal Trip Release Configuration

    series trip single location

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.800 minimum at 150 pct and 2.750 maximum at 150 pct and 0.350 minimum at 200 pct and 1.000 maximum at 200 pct and 0.150 minimum at 300 pct and 0.400 maximum at 300 pct single location

  • Inclosure Protection Type For Which Designed

    fungus resistant and moisture resistant and explosion resistant

  • Frequency In Hertz

    60.0 single location

  • Case Material

    plastic

  • Center To Center Distance Between Terminals Parallel To Length

    4.359 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.000 inches nominal

  • Iii Storage Type

    general purpose warehouse

  • Maximum Continuous Load Current Rating Per Pole

    15.0 amperes ac single location

Related Manufacturers

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...