NSN: 5925-00-918-1474
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac single location
-
Pole Quantity
1
-
Manual Actuator Type And Quantity
1 toggle
-
Nominal Thread Size
0.138 inches
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Main Contact Tripping Mechanism Type
trip free
-
Arc Quenching Method
magnetic blowout
-
Overall Width
0.760 inches nominal
-
Frequency In Hertz
60.0 single location
-
Overall Length
3.330 inches nominal
-
Trip Release Characteristic
instantaneous single location and time delay single location
-
Maximum Continuous Load Current Rating Per Pole
7.5 amperes ac single location
-
Case Material
plastic
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.062 inches nominal
-
Terminal Type And Quantity
2 threaded stud
-
Actuator Function
reset
-
Inclosure Protection Type For Which Designed
fungus resistant and explosion proof and moisture resistant
-
Trip Release Method
magnetic single location
-
Thread Series Designator
unc
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac single location
-
Reset Method
manual
-
Overall Height
2.530 inches nominal
-
Mounting Facility Type And Quantity
2 threaded hole
-
Thread Quantity Per Inch
32
-
Circuit Protection Type
overcurrent single location
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.250 minimum at 200 pct single location and 2.000 maximum at 150 pct single location and 0.800 maximum at 200 pct single location and 0.600 minimum at 150 pct single location and 0.090 minimum at 300 pct single location and 0.190 maximum at 300 pct
-
~1
single location