Technical Characteristics

  • Trip Release Method

    thermal single location

  • Manual Actuator Type And Quantity

    1 push-pull

  • Inclosure Protection Type For Which Designed

    fungus resistant and moisture resistant

  • Pole Quantity

    1

  • Internal Trip Release Configuration

    series trip single location

  • Nominal Thread Size

    0.138 inches

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    1.822 inches maximum

  • Trip Release Characteristic

    time delay single location

  • Main Contact Tripping Mechanism Type

    trip free

  • Frequency In Hertz

    400.0 single location

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    3500.0 ac single location and 6000.0 dc single location

  • Body Style

    single pole type

  • Body Length

    2.187 inches maximum

  • Operating Voltage Type And Rating Per Pole In Volts

    120.0 ac single location and 30.0 dc single location

  • Maximum Continuous Load Current Rating Per Pole

    10.0 amperes ac single location and 10.0 amperes dc single location

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    138.0 single location

  • Trip Delay Time In Seconds Per Rated Continuous Current

    45.000 minimum at 150 pct single location and 15.000 minimum at 200 pct single location and 105.000 maximum at 150 pct single location and 50.000 maximum at 200 pct single location

  • Bushing Length

    0.250 inches maximum

  • Body Width

    0.750 inches maximum

  • Case Material

    plastic

  • Thread Series Designator

    unc

  • Reset Method

    manual

  • Center To Center Distance Between Terminals Parallel To Length

    1.187 inches nominal

  • Trip Release Ambient Temp Rating

    25.0 deg celsius maximum single location

  • Actuator Position Designation

    at pole one

  • Storage Type

    general purpose warehouse

  • Actuator Function

    trip-reset

  • Terminal Type And Quantity

    2 screw

  • Mounting Facility Type And Quantity

    2 threaded hole

  • Thread Quantity Per Inch

    32

  • Mounting Surface To Terminal End Distance

    2.000 inches maximum

  • Circuit Protection Type

    overcurrent single location

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...