Technical Characteristics

  • Trip Delay Time In Seconds Per Rated Continuous Current

    10.000 minimum at 150 pct single location and 1.400 minimum at 300 pct single location and 30.000 maximum at 150 pct single location and 10.000 maximum at 200 pct single location and 4.000 minimum at 200 pct single location and 4.000 maximum at 300 pct

  • ~1

    single location

  • Trip Release Characteristic

    time delay single location

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 single location

  • Main Contact Tripping Mechanism Type

    trip free

  • Arc Quenching Method

    magnetic blowout

  • Ultimate Trip Time Per Pole In Seconds

    18.000 minimum single location and 70.000 maximum single location

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.052 inches minimum and 2.072 inches maximum

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    2000.0 ac single location

  • Body Style

    single pole type

  • Manual Actuator Type And Quantity

    2 toggle

  • Trip Release Method

    magnetic-hydraulic single location

  • Frequency In Hertz

    60.0 single location

  • Auxiliary Switch Function And Quantity

    1 alarm

  • Operating Voltage Type And Rating Per Pole In Volts

    125.0 ac single location

  • Terminal Type And Quantity

    2 threaded stud

  • Body Length

    2.490 inches minimum and 2.510 inches maximum

  • Boss Height

    0.130 inches minimum and 0.150 inches maximum

  • Switch Location And Position Designation

    internal at pole one

  • Case Material

    plastic

  • Fragility Factor

    moderately rugged

  • Inclosure Protection Type For Which Designed

    explosion resistant and fungus resistant and moisture resistant

  • Switch Terminal Type

    tab, solder lug

  • Thread Series Designator

    unc

  • Maximum Continuous Load Current Rating Per Pole

    25.0 amperes ac single location

  • Reset Method

    manual

  • Mounting Surface To Terminal End Distance

    2.461 inches minimum and 2.481 inches maximum

  • Center To Center Distance Between Terminals Parallel To Length

    1.928 inches minimum and 1.948 inches maximum

  • Actuator Position Designation

    at pole one

  • Storage Type

    general purpose warehouse

  • Actuator Function

    trip-reset

  • Mounting Facility Type And Quantity

    2 threaded hole

  • Thread Quantity Per Inch

    32

  • Body Width

    0.740 inches minimum and 0.760 inches maximum

  • Circuit Protection Type

    overcurrent single location

  • Switch Contact Arrangement

    single pole, double throw

  • Switch Current Rating And Type In Amps

    2.5 ac and 1.0 dc

  • Switch Voltage Rating And Type In Volts

    250.0 ac and 50.0 dc

  • Pole Quantity

    1

  • Internal Trip Release Configuration

    series trip single location

  • Nominal Thread Size

    0.138 inches

Related Manufacturers

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...