NSN: 5925-00-923-0079

Circuit Breakers

CIRCUIT BREAKER

5925 - Circuit Breakers

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Center To Center Distance Between Terminals Parallel To Length

    1.928 inches minimum and 1.948 inches maximum

  • Storage Type

    general purpose warehouse

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • Internal Trip Release Configuration

    series trip all locations

  • Mounting Surface To Terminal End Distance

    2.461 inches minimum and 2.481 inches maximum

  • Reset Method

    manual

  • Actuator Position Designation

    at each pole

  • Thread Series Designator

    unc

  • Pole Quantity

    2

  • Circuit Protection Type

    overcurrent all locations

  • Fragility Factor

    moderately rugged

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations

  • Mounting Facility Type And Quantity

    4 threaded hole

  • Thread Quantity Per Inch

    32

  • Trip Release Method

    magnetic-hydraulic all locations

  • Body Style

    multipole-multiple actuator type

  • Inclosure Protection Type For Which Designed

    fungus resistant

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    150.0 all locations

  • Maximum Continuous Load Current Rating Per Pole

    5.0 amperes ac all locations

  • Nominal Thread Size

    0.138 inches

  • Center To Center Distance Between Terminals Parallel To Width

    0.740 inches minimum and 0.760 inches maximum

  • Body Width

    1.490 inches minimum and 1.510 inches maximum

  • Frequency In Hertz

    60.0 all locations

  • Main Contact Tripping Mechanism Type

    trip free

  • Arc Quenching Method

    magnetic blowout

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.052 inches minimum and 2.072 inches maximum

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.740 inches minimum and 0.760 inches maximum

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac all locations

  • Manual Actuator Type And Quantity

    2 toggle

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.300 minimum at 200 pct all locations and 1.000 maximum at 200 pct all locations

  • Body Length

    2.490 inches minimum and 2.510 inches maximum

  • Terminal Type And Quantity

    4 threaded stud

  • External Actuator Linkage Arrangement

    one and two linked

  • Boss Height

    0.130 inches minimum and 0.150 inches maximum

  • Case Material

    plastic

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...