NSN: 5925-00-923-2118
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
2
-
Actuator Function
trip w/separate reset
-
Reset Method
manual
-
Trip Release Characteristic
time delay all locations
-
Overall Width
3.500 inches nominal
-
Terminal Type And Quantity
4 screw
-
Overall Length
6.500 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
22.000 nominal at 200 pct all locations and 160.000 nominal at 125 pct all locations and 5.000 nominal at 300 pct all locations
-
Mounting Facility Type And Quantity
3 unthreaded hole
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Maximum Continuous Load Current Rating Per Pole
70.0 amperes ac all locations and 70.0 amperes dc all locations
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal all locations
-
Arc Quenching Method
deion
-
Main Contact Tripping Mechanism Type
trip free
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
10000.0 ac all locations and 10000.0 dc all locations
-
Nominal Thread Size
0.164 inches
-
Trip Release Duty Cycle
continuous all locations
-
Unthreaded Mounting Hole Diameter
0.188 inches nominal
-
Thread Series Designator
un
-
Special Features
mtg holes irregularly spaced
-
Operating Voltage Type And Rating Per Pole In Volts
480.0 ac all locations and 250.0 dc all locations
-
Overall Height
2.750 inches nominal
-
Case Material
plastic
-
Trip Release Method