NSN: 5925-00-941-8194
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Actuator Function
reset
-
Thread Series Designator
unc
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1500.0 ac single location
-
Reset Method
manual
-
Trip Release Ambient Temp Rating
25.0 deg celsius maximum single location
-
Center To Center Distance Between Terminals Parallel To Length
1.890 inches nominal
-
Terminal Type And Quantity
2 screw
-
Inclosure Protection Type For Which Designed
fungus resistant and hermetically sealed
-
Nominal Thread Size
0.375 inches
-
Circuit Protection Type
overcurrent single location
-
Trip Release Method
thermal single location
-
Mounting Facility Type And Quantity
1 threaded bushing
-
Manual Actuator Type And Quantity
1 push-pull
-
Mounting Surface To Terminal End Distance
2.260 inches nominal
-
Thread Quantity Per Inch
27
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac single location and 24.0 dc single location
-
Pole Quantity
1
-
Internal Trip Release Configuration
series trip single location
-
Trip Release Characteristic
time delay single location
-
Main Contact Tripping Mechanism Type
trip free
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac single location and 15.0 amperes dc single location
-
Body Style
single pole type
-
Bushing Length
0.390 inches nominal
-
Body Width
0.570 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
7.000 nominal at 300 pct single location
-
Body Length
1.140 inches nominal
-
Case Material
plastic