NSN: 5925-00-963-1280

Circuit Breakers

CIRCUIT BREAKER

5925 - Circuit Breakers

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Trip Release Ambient Temp Rating

    50.0 deg celsius nominal all locations

  • Frequency In Hertz

    400.0 all locations

  • Terminal Type And Quantity

    6 threaded stud

  • Body Style

    17b multipole-single actuator type

  • Body Length

    10.000 inches maximum

  • Unthreaded Mounting Hole Diameter

    0.500 inches nominal

  • Iii Fragility Factor

    moderately rugged

  • Boss Height

    0.188 inches nominal

  • Mounting Surface To Terminal End Distance

    7.531 inches maximum

  • Mounting Facility Type And Quantity

    4 unthreaded hole

  • Circuit Protection Type

    overcurrent all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    150.0 all locations

  • Reset Method

    manual

  • Actuator Function

    trip-reset

  • Body Width

    5.000 inches maximum

  • Case Material

    plastic

  • Center To Center Distance Between Terminals Parallel To Length

    8.750 inches nominal

  • Center To Center Distance Between Terminals Parallel To Width

    1.625 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    8.750 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.625 inches nominal

  • Pole Quantity

    3

  • Iii Arc Quenching Method

    magnetic blowout

  • Iii Storage Type

    general purpose warehouse

  • Iii Special Handling Feature

    magnetic

  • Maximum Continuous Load Current Rating Per Pole

    50.0 amperes ac all locations

  • Operating Voltage Type And Rating Per Pole In Volts

    500.0 ac all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    10000.0 ac all locations

  • Trip Release Method

    thermal-magnetic all locations

  • Trip Release Characteristic

    time delay all locations

  • Ultimate Trip Time Per Pole In Seconds

    3610.000 nominal all locations

  • Main Contact Tripping Mechanism Type

    trip free

  • Manual Actuator Type And Quantity

    1 toggle

  • Actuator Position Designation

    at pole two

  • Trip Delay Time In Seconds Per Rated Continuous Current

    20.000 minimum at 600 pct and 32.000 maximum at 600 pct all locations

  • Inclosure Protection Type For Which Designed

    general purpose

  • Iii Unpackaged Unit Weight

    5.500 pounds

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...