NSN: 5925-00-965-8497
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Inclosure Protection Type For Which Designed
dustproof
-
Overall Width
6.687 inches nominal
-
Reset Method
manual
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations
-
Case Material
metal
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal all locations
-
Arc Quenching Method
deion
-
Manual Actuator Type And Quantity
1 toggle
-
Maximum Continuous Load Current Rating Per Pole
40.0 amperes ac all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
115.0 all locations
-
Overall Length
13.093 inches nominal
-
Trip Release Duty Cycle
continuous all locations
-
Special Features
flush mtd on 11.750 in. by 8.000 in. mtg centers
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
7500.0 ac all locations
-
Terminal Type And Quantity
6 pin
-
Nominal Thread Size
0.250 inches
-
Trip Delay Time In Seconds Per Rated Continuous Current
3.000 minimum at 500 pct all locations and 30.000 minimum at 150 pct all locations and 240.000 maximum at 150 pct all locations and 5.000 maximum at 500 pct all locations
-
Overall Height
9.625 inches nominal
-
Trip Release Method
thermal all locations