NSN: 5925-00-985-0104

Circuit Breakers

CIRCUIT BREAKER

5925 - Circuit Breakers

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Operating Voltage Type And Rating Per Pole In Volts

    208.0 ac all locations

  • Pole Quantity

    3

  • Circuit Protection Type

    overcurrent all locations

  • Maximum Continuous Load Current Rating Per Pole

    50.0 amperes ac all locations

  • Reset Method

    manual

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • Internal Trip Release Configuration

    series trip all locations

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    4.359 inches nominal

  • Body Length

    5.250 inches nominal

  • Trip Release Method

    magnetic-hydraulic all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Actuator Position Designation

    at pole two

  • Body Style

    multipole-single actuator type

  • Center To Center Distance Between Terminals Parallel To Width

    1.000 inches nominal

  • Body Width

    3.000 inches nominal

  • Manual Actuator Type And Quantity

    1 toggle

  • Frequency In Hertz

    60.0 all locations

  • Terminal Type And Quantity

    6 compression

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.000 inches nominal

  • Main Contact Tripping Mechanism Type

    trip free

  • Mounting Facility Type And Quantity

    4 unthreaded hole

  • Mounting Surface To Terminal End Distance

    2.687 inches nominal

  • Boss Height

    0.218 inches nominal

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    5000.0 ac all locations

  • Trip Delay Time In Seconds Per Rated Continuous Current

    38.000 minimum at 200 pct all locations and 120.000 maximum at 200 pct all locations

  • Center To Center Distance Between Terminals Parallel To Length

    4.359 inches nominal

  • Unthreaded Mounting Hole Diameter

    0.190 inches nominal

  • Ultimate Trip Time Per Pole In Seconds

    150.000 minimum all locations and 550.000 maximum all locations

  • Case Material

    plastic

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...