NSN: 5925-00-994-3398
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Case Material
plastic
-
Trip Release Method
thermal all locations
-
Terminal Type And Quantity
6 threaded stud
-
Bushing Length
0.250 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
208.0 ac all locations
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Reset Method
manual
-
Thread Series Designator
unf
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations
-
Thread Quantity Per Inch
32
-
Body Style
multipole-multiple actuator type
-
Mounting Facility Type And Quantity
1 threaded bushing
-
Manual Actuator Type And Quantity
1 push-pull
-
Actuator Position Designation
at pole two
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal all locations
-
Body Width
1.300 inches maximum
-
Maximum Continuous Load Current Rating Per Pole
5.0 amperes ac all locations
-
Frequency In Hertz
60.0 all locations
-
Center To Center Distance Between Terminals Parallel To Length
1.376 inches nominal
-
Inclosure Protection Type For Which Designed
explosion proof
-
Main Contact Tripping Mechanism Type
trip free
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
138.0 all locations
-
Body Length
2.063 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.830 minimum at 200 pct all locations and 1.500 maximum at 200 pct all locations
-
Mounting Surface To Terminal End Distance
1.875 inches maximum
-
Nominal Thread Size
0.469 inches
-
Center To Center Distance Between Terminals Parallel To Width
0.750 inches nominal