NSN: 5925-00-994-9138
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Height
2.687 inches nominal
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Length
4.359 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
0.984 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.984 inches nominal
-
Fragility Factor
moderately rugged
-
Arc Quenching Method
magnetic blowout
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Special Handling Feature
magnetic
-
Circuit Protection Type
overcurrent single location
-
Trip Release Characteristic
time delay single location
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Switch Location And Position Designation
internal at pole one
-
Switch Terminal Type
screw
-
Terminal Type And Quantity
6 threaded stud
-
Body Width
3.000 inches nominal
-
Body Style
9b multipole-single actuator type
-
Body Length
5.240 inches minimum and 5.260 inches maximum
-
Unthreaded Mounting Hole Diameter
0.190 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
3.063 inches nominal
-
Switch Contact Arrangement
single pole, double throw
-
Boss Height
0.218 inches nominal
-
Mounting Surface To Terminal End Distance
3.389 inches minimum and 3.409 inches maximum
-
Pole Quantity
3
-
Storage Type
general purpose warehouse
-
Maximum Continuous Load Current Rating Per Pole
25.0 amperes ac all locations
-
Operating Voltage Type And Rating Per Pole In Volts
208.0 ac all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac all locations
-
Trip Release Method
magnetic-hydraulic single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Function
trip-reset
-
Actuator Position Designation
at pole two
-
Auxiliary Switch Function And Quantity
1 alarm
-
Internal Trip Release Configuration
series trip single location
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.450 minimum at 200 pct single location and 1.000 maximum at 200 pct
-
Inclosure Protection Type For Which Designed
dustproof
-
Switch Current Rating And Type In Amps
15.0 ac and 15.0 dc
-
Switch Voltage Rating And Type In Volts
460.0 ac and 250.0 dc
-
Frequency In Hertz
60.0 all locations