NSN: 5925-01-004-6432
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Reset Method
manual
-
Manual Actuator Type And Quantity
3 toggle
-
Actuator Position Designation
at each pole
-
Trip Delay Time In Seconds Per Rated Continuous Current
50.000 nominal at 125 pct and 0.900 nominal at 400 pct
-
Body Style
multipole-multiple actuator type
-
Body Length
2.490 inches nominal
-
Body Width
2.250 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
0.750 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.060 inches nominal
-
Boss Height
0.150 inches nominal
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac and 1000.0 dc
-
Circuit Protection Type
overcurrent
-
Trip Release Characteristic
time delay
-
Nominal Thread Size
0.138 inches
-
Trip Release Duty Cycle
continuous
-
Special Features
inertial overload provision prevent trip during short transient spikes
-
Frequency In Hertz
60.0
-
Thread Series Designator
unc
-
Terminal Type And Quantity
6 threaded stud
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Length
1.940 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.750 inches nominal
-
Mounting Surface To Terminal End Distance
2.475 inches nominal
-
Pole Quantity
3
-
Mounting Facility Type And Quantity
6 threaded hole
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac and 15.0 amperes dc
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac and 50.0 dc
-
Trip Release Method
magnetic-hydraulic
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Ultimate Trip Time Per Pole In Seconds
50.000 nominal
-
Main Contact Tripping Mechanism Type
trip free
-
Actuator Function
trip-reset
-
External Actuator Linkage Arrangement
one,two,and three linked
-
Internal Trip Release Configuration
series trip