NSN: 5925-01-009-0195
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Thread Series Designator
unc
-
Inclosure Protection Type For Which Designed
explosion proof and shockproof and vibrationproof
-
Trip Delay Time In Seconds Per Rated Continuous Current
1.000 minimum at 200 pct and 7.000 maximum at 200 pct
-
Nominal Thread Size
0.138 inches
-
Internal Trip Release Configuration
series trip
-
Trip Release Method
magnetic
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 dc
-
Operating Voltage Type And Rating Per Pole In Volts
50.0 dc
-
Maximum Continuous Load Current Rating Per Pole
35.0 amperes dc
-
Thread Quantity Per Inch
32
-
Storage Type
general purpose warehouse
-
Mounting Facility Type And Quantity
2 threaded hole
-
Pole Quantity
1
-
Mounting Surface To Terminal End Distance
2.375 inches minimum and 2.515 inches maximum
-
Case Material
plastic
-
Body Width
0.740 inches minimum and 0.760 inches maximum
-
Body Length
2.490 inches minimum and 2.510 inches maximum
-
Body Style
single pole type
-
Terminal Type And Quantity
2 threaded stud
-
Test Data Document
82577-918203 drawing
-
Unpackaged Unit Weight
4.000 ounces
-
Actuator Position Designation
at pole one
-
Actuator Function
trip-reset
-
Manual Actuator Type And Quantity
1 toggle
-
Main Contact Tripping Mechanism Type
trip free
-
Reset Method
manual
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Trip Release Characteristic
time delay
-
Circuit Protection Type
overcurrent
-
Special Handling Feature
magnetic
-
Arc Quenching Method
magnetic blowout
-
Boss Height
0.090 inches minimum and 0.165 inches maximum
-
Fragility Factor
moderately rugged
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.052 inches minimum and 2.072 inches maximum
-
Center To Center Distance Between Terminals Parallel To Length
1.928 inches minimum and 1.948 inches maximum