NSN: 5925-01-017-0018
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Frequency In Hertz
60.0 all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Trip Delay Time In Seconds Per Rated Continuous Current
11.000 minimum at 200 pct all locations and 29.000 maximum at 200 pct all locations
-
Boss Height
0.219 inches nominal
-
Manual Actuator Type And Quantity
2 toggle
-
Body Width
2.000 inches nominal
-
Mounting Facility Type And Quantity
4 terminal
-
External Actuator Linkage Arrangement
one and two linked
-
Terminal Type And Quantity
2 clip and 2 compression
-
Case Material
plastic
-
Body Length
3.344 inches nominal
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
2
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Storage Type
general purpose warehouse
-
Body Height
2.312 inches nominal
-
Trip Release Ambient Temp Rating
40.0 deg celsius nominal all locations
-
Actuator Function
trip-reset
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations
-
Unpackaged Unit Weight
12.500 ounces
-
Maximum Continuous Load Current Rating Per Pole
125.0 amperes ac all locations
-
Body Style
multipole-multiple actuator type
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Trip Release Method
thermal-magnetic all locations
-
Inclosure Protection Type For Which Designed
fungus resistant
-
Center To Center Distance Between Terminals Parallel To Width
1.000 inches nominal
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
10000.0 ac all locations