NSN: 5925-01-022-7719

Technical Characteristics

  • Trip Release Method

    magnetic all locations

  • Body Style

    multipole-multiple actuator type

  • Inclosure Protection Type For Which Designed

    shock resistant and fungus resistant and salt spray proof and moisture resistant and vibration resistant

  • Fragility Factor

    moderately rugged

  • Center To Center Distance Between Terminals Parallel To Width

    0.750 inches nominal

  • Center To Center Distance Between Terminals Parallel To Length

    1.660 inches minimum and 1.960 inches maximum

  • Special Handling Feature

    magnetic

  • Pole Quantity

    3

  • Circuit Protection Type

    overcurrent all locations

  • Thread Series Designator

    unc

  • Actuator Position Designation

    at each pole

  • Reset Method

    manual

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.046 inches minimum and 2.078 inches maximum

  • Storage Type

    general purpose warehouse

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • External Actuator Linkage Arrangement

    one, two, and three linked

  • Internal Trip Release Configuration

    series trip all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations

  • Thread Quantity Per Inch

    32

  • Operating Voltage Type And Rating Per Pole In Volts

    240.0 ac all locations

  • Body Width

    2.205 inches minimum and 2.285 inches maximum

  • Test Data Document

    81349-mil-c-55629 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type

  • ~1

    data on certain environmental and performanc

  • Mounting Surface To Terminal End Distance

    2.553 inches maximum

  • Mounting Facility Type And Quantity

    6 threaded hole

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    150.0 all locations

  • Nominal Thread Size

    0.138 inches

  • Main Contact Tripping Mechanism Type

    trip free

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.750 inches nominal

  • Arc Quenching Method

    magnetic blowout

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.150 minimum at 200 pct all locations and 1.900 maximum at 200 pct all locations

  • Boss Height

    0.140 inches nominal

  • Maximum Continuous Load Current Rating Per Pole

    30.0 amperes ac all locations

  • Frequency In Hertz

    400.0 all locations

  • Specification/Standard Data

    81349-mil-c-55629/5 government specification

  • Thread Pitch Diameters

    +0.1177/+0.1214 inches

  • Body Length

    2.510 inches maximum

  • Manual Actuator Type And Quantity

    3 toggle

  • Case Material

    plastic

  • Terminal Type And Quantity

    6 threaded stud

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...