NSN: 5925-01-026-8097
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Center To Center Distance Between Terminals Parallel To Length
0.865 inches minimum and 0.885 inches maximum
-
Mounting Surface To Terminal End Distance
1.855 inches maximum
-
Mounting Facility Type And Quantity
1 threaded bushing
-
Thread Quantity Per Inch
32
-
Operating Voltage Type And Rating Per Pole In Volts
50.0 dc
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
500.0 dc
-
Trip Release Characteristic
time delay
-
Reset Method
manual
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Position Designation
at each pole
-
Nominal Thread Size
0.375 inches
-
Trip Release Duty Cycle
continuous
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal
-
Special Test Features
navord od41152
-
Terminal Type And Quantity
4 wire hook
-
Bushing Length
0.310 inches minimum and 0.370 inches maximum
-
Body Length
1.531 inches maximum
-
Body Width
1.250 inches maximum
-
Case Material
metal
-
Center To Center Distance Between Terminals Parallel To Width
0.594 inches minimum and 0.656 inches maximum
-
Pole Quantity
2
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes dc
-
Circuit Protection Type
overcurrent
-
Trip Release Method
magnetic
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Main Contact Tripping Mechanism Type
trip free
-
Actuator Function
reset
-
Internal Trip Release Configuration
series trip
-
Trip Delay Time In Seconds Per Rated Continuous Current
6.000 maximum at 125 pct
-
Thread Series Designator
unef
-
Reference Number Differentiating Characteristics
as differentiated by special test features