NSN: 5925-01-027-6442
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Pole Quantity
1
-
Arc Quenching Method
magnetic blowout
-
Mounting Facility Type And Quantity
2 threaded hole
-
Maximum Continuous Load Current Rating Per Pole
3.0 amperes dc
-
Operating Voltage Type And Rating Per Pole In Volts
65.0 dc
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 dc
-
Circuit Protection Type
overcurrent
-
Trip Release Method
magnetic-hydraulic
-
Trip Release Characteristic
time delay
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Reset Method
manual
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Function
trip-reset
-
Actuator Position Designation
at pole one
-
Auxiliary Switch Function And Quantity
1 alarm
-
Thread Series Designator
unc
-
Unpackaged Unit Weight
2.500 ounces
-
Switch Current Rating And Type In Amps
10.0 ac and 5.0 dc
-
Switch Terminal Type
quick disconnect,male
-
Nominal Thread Size
0.138 inches
-
Internal Trip Release Configuration
series trip
-
Main Contact Tripping Mechanism Type
trip free
-
Thread Quantity Per Inch
32
-
Storage Type
general purpose warehouse
-
Mounting Surface To Terminal End Distance
1.875 inches minimum and 1.885 inches maximum
-
Boss Height
0.125 inches minimum and 0.135 inches maximum
-
Fragility Factor
moderately rugged
-
Switch Contact Arrangement
single pole,double throw
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.655 inches minimum and 1.655 inches maximum
-
Center To Center Distance Between Terminals Parallel To Length
1.555 inches minimum and 1.565 inches maximum
-
Case Material
plastic
-
Body Width
0.745 inches minimum and 0.755 inches maximum
-
Body Length
1.985 inches minimum and 2.015 inches maximum
-
Body Style
single pole type
-
Terminal Type And Quantity
2 quick disconnect,male
-
Switch Voltage Rating And Type In Volts
250.0 ac and 30.0 dc
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.900 minimum at 200 pct and 12.000 maximum at 200 pct
-
Switch Location And Position Designation
internal at pole one