Technical Characteristics

  • Pole Quantity

    3

  • Circuit Protection Type

    overcurrent all locations

  • Inclosure Protection Type For Which Designed

    dustproof

  • Thread Series Designator

    unc

  • Reset Method

    manual

  • Center To Center Distance Between Terminals Parallel To Width

    1.500 inches nominal

  • Trip Release Ambient Temp Rating

    40.0 deg celsius nominal all locations

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • Operating Voltage Type And Rating Per Pole In Volts

    600.0 ac all locations and 250.0 dc all locations

  • Mounting Facility Type And Quantity

    4 threaded hole

  • Thread Quantity Per Inch

    32

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    5.125 inches nominal

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Trip Release Method

    thermal-magnetic all locations

  • Body Height

    3.000 inches nominal

  • Actuator Position Designation

    at pole two

  • Body Style

    multipole-single actuator type

  • Center To Center Distance Between Terminals Parallel To Length

    5.125 inches nominal

  • Manual Actuator Type And Quantity

    1 toggle

  • Body Width

    4.344 inches nominal

  • Frequency In Hertz

    60.0 all locations

  • Terminal Type And Quantity

    6 compression

  • Main Contact Tripping Mechanism Type

    trip free

  • Nominal Thread Size

    0.164 inches

  • Boss Height

    0.125 inches nominal

  • Maximum Continuous Load Current Rating Per Pole

    40.0 amperes ac all locations and 40.0 amperes dc all locations

  • Body Length

    6.000 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.500 inches nominal

  • Trip Delay Time In Seconds Per Rated Continuous Current

    30.000 minimum at 200 pct all locations and 100.000 maximum at 200 pct all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    18000.0 ac all locations and 10000.0 dc all locations

  • Case Material

    plastic

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...