Technical Characteristics
-
Fragility Factor
moderately rugged
-
Switch Terminal Type
tab, solder lug
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Reset Method
manual
-
Switch Location And Position Designation
internal at pole three
-
Storage Type
general purpose warehouse
-
Body Width
1.844 inches minimum and 1.906 inches maximum
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Inclosure Protection Type For Which Designed
moisture resistant and hermetically sealed
-
Internal Trip Release Configuration
series trip all locations
-
Switch Voltage Rating And Type In Volts
125.0 ac and 50.0 dc
-
Thread Pitch Diameters
+0.3503/+0.3537 inches
-
Nominal Thread Size
0.375 inches
-
Thread Quantity Per Inch
32
-
Switch Current Rating And Type In Amps
1.0 ac and 0.5 dc
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
300.0 ac all locations
-
Mounting Surface To Terminal End Distance
1.690 inches minimum and 1.710 inches maximum
-
Terminal Type And Quantity
6 wire hook
-
Auxiliary Switch Function And Quantity
1 alarm
-
Center To Center Distance Between Terminals Parallel To Width
0.615 inches minimum and 0.635 inches maximum
-
Thread Series Designator
unef
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations
-
Bushing Length
0.365 inches minimum and 0.385 inches maximum
-
Arc Quenching Method
magnetic blowout
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
115.0 all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Frequency In Hertz
60.0 all locations
-
Manual Actuator Type And Quantity
1 toggle
-
Center To Center Distance Between Terminals Parallel To Length
0.865 inches minimum and 0.885 inches maximum
-
Case Material
metal
-
Body Length
1.552 inches minimum and 1.572 inches maximum
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.500 minimum at 200 pct all locations and 4.500 maximum at 200 pct all locations
-
Body Style
multipole-single actuator type
-
Switch Contact Arrangement
single pole, double throw
-
Maximum Continuous Load Current Rating Per Pole
3.0 amperes ac all locations
-
Actuator Position Designation
at pole two
-
Mounting Facility Type And Quantity
1 threaded bushing
-
Trip Release Method
magnetic-hydraulic all locations