Technical Characteristics

  • Fragility Factor

    moderately rugged

  • Center To Center Distance Between Terminals Parallel To Width

    0.750 inches nominal

  • Circuit Protection Type

    overcurrent all locations

  • Inclosure Protection Type For Which Designed

    dustproof

  • Pole Quantity

    2

  • Thread Series Designator

    unc

  • Actuator Position Designation

    at each pole

  • Reset Method

    manual

  • Switch Terminal Type

    turret

  • Storage Type

    general purpose warehouse

  • Switch Current Rating And Type In Amps

    5.0 ac and 1.0 dc

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • Internal Trip Release Configuration

    series trip all locations

  • Switch Voltage Rating And Type In Volts

    125.0 ac and 50.0 dc

  • Mounting Facility Type And Quantity

    4 threaded hole

  • Thread Quantity Per Inch

    32

  • Trip Release Method

    magnetic-hydraulic all locations

  • Arc Quenching Method

    air

  • Mounting Surface To Terminal End Distance

    2.611 inches nominal

  • Body Style

    multipole-multiple actuator type

  • Trip Delay Time In Seconds Per Rated Continuous Current

    2.500 minimum at 200 pct all locations and 7.500 maximum at 200 pct all locations

  • Switch Contact Arrangement

    single pole, double throw

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    150.0 all locations

  • Maximum Continuous Load Current Rating Per Pole

    8.0 amperes dc all locations

  • Nominal Thread Size

    0.138 inches

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    3000.0 dc all locations

  • Switch Location And Position Designation

    external at pole one

  • Main Contact Tripping Mechanism Type

    trip free

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.750 inches nominal

  • Body Length

    2.500 inches nominal

  • Boss Height

    0.140 inches nominal

  • Operating Voltage Type And Rating Per Pole In Volts

    32.0 dc all locations

  • Manual Actuator Type And Quantity

    2 toggle

  • Auxiliary Switch Function And Quantity

    1 alarm

  • Terminal Type And Quantity

    4 threaded stud

  • Body Width

    1.500 inches nominal

  • External Actuator Linkage Arrangement

    one and two linked

  • Case Material

    plastic

  • Center To Center Distance Between Terminals Parallel To Length

    1.938 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.062 inches nominal

Related Manufacturers

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...