NSN: 5925-01-054-3783
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Arc Quenching Method
magnetic blowout
-
Unpackaged Unit Weight
3.600 ounces
-
Nonturn Device Diameter
0.157 inches minimum and 0.219 inches maximum
-
Body Width
1.250 inches maximum
-
Trip Delay Time In Seconds Per Rated Continuous Current
90.000 maximum at 200 pct second location
-
Thread Series Designator
unef
-
Inclosure Protection Type For Which Designed
shock resistant and hermetically sealed and vibration resistant
-
Center To Center Distance Between Terminals Parallel To Length
0.844 inches minimum and 0.906 inches maximum
-
Features Provided
high inrush protection
-
Bushing Length
0.380 inches maximum
-
Case Material
plastic
-
Fragility Factor
moderately rugged
-
Trip Delay Time In Seconds Per Rated Continuous Current
30.000 minimum at 200 pct second location and 0.500 minimum at 200 pct first location and 11.000 maximum at 100 pct first location
-
Special Handling Feature
magnetic
-
Circuit Protection Type
overcurrent all locations
-
Criticality Code Justification
cbbl
-
Pole Quantity
2
-
Center To Center Distance Between Terminals Parallel To Width
0.344 inches minimum and 0.406 inches maximum
-
Reset Method
manual
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Storage Type
general purpose warehouse
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations
-
Maximum Continuous Load Current Rating Per Pole
2.5 amperes ac second location
-
Nominal Thread Size
0.375 inches
-
Thread Quantity Per Inch
32
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations
-
Trip Release Method
magnetic all locations
-
Nonturn Device Radius
0.594 inches minimum and 0.656 inches maximum
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Mounting Surface To Terminal End Distance
1.780 inches maximum
-
Terminal Type And Quantity
4 wire hook
-
Nonturn Device Location
at 3 oclock and at 9 oclock
-
Body Style
multipole-single actuator type
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes ac first location
-
Manual Actuator Type And Quantity
1 toggle
-
Frequency In Hertz
60.0 all locations
-
Body Length
1.500 inches maximum
-
Actuator Position Designation
between pole one and two
-
Main Contact Tripping Mechanism Type
trip free