NSN: 5925-01-061-7108
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Switch Current Rating And Type In Amps
10.0 ac
-
Frequency In Hertz
60.0
-
Unpackaged Unit Weight
2.700 pounds
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Length
3.550 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.750 inches nominal
-
Switch Contact Arrangement
single pole,double throw
-
Fragility Factor
moderately rugged
-
Pole Quantity
4
-
Mounting Facility Type And Quantity
8 threaded hole
-
Maximum Continuous Load Current Rating Per Pole
250.0 milliamperes ac
-
Circuit Protection Type
overcurrent
-
Trip Release Characteristic
time delay
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Ultimate Trip Time Per Pole In Seconds
800.000 maximum
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
4 toggle
-
Actuator Function
trip-reset
-
External Actuator Linkage Arrangement
one,two,three,and four linked
-
Auxiliary Switch Function And Quantity
1 alarm
-
Nominal Thread Size
0.138 inches
-
Switch Location And Position Designation
external at pole one
-
Body Length
5.125 inches nominal
-
Body Width
4.144 inches maximum
-
Center To Center Distance Between Terminals Parallel To Width
1.026 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.026 inches nominal
-
Boss Height
0.220 inches nominal
-
Mounting Surface To Terminal End Distance
3.550 inches nominal
-
Arc Quenching Method
magnetic blowout
-
Storage Type
general purpose warehouse
-
Features Provided
high inrush protection
-
Thread Quantity Per Inch
32
-
Operating Voltage Type And Rating Per Pole In Volts
277.0 ac and 480.0 ac
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac
-
Trip Release Method
magnetic-hydraulic
-
Actuator Position Designation
at each pole
-
Internal Trip Release Configuration
series trip
-
Trip Delay Time In Seconds Per Rated Continuous Current
70.000 minimum at 125 pct and 800.000 maximum at 125 pct and 20.000 minimum at 200 pct and 130.000 maximum at 200 pct and 4.000 minimum at 400 pct and 18.000 maximum at 400 pct and 0.012 minimum at 1000 pct and 0.080 maximum at 1000 pct
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Switch Terminal Type
tab,solder lug
-
Switch Voltage Rating And Type In Volts
250.0 ac
-
Special Features
anti-flashover barrier between poles
-
Thread Series Designator
unc
-
Terminal Type And Quantity
8 threaded stud