NSN: 5925-01-064-7826

Circuit Breakers

CIRCUIT BREAKER

5925 - Circuit Breakers

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Center To Center Distance Between Terminals Parallel To Length

    1.928 inches minimum and 1.948 inches maximum

  • Actuator Position Designation

    at pole one

  • Maximum Continuous Load Current Rating Per Pole

    3.0 amperes ac single location

  • Storage Type

    general purpose warehouse

  • Actuator Function

    trip-reset

  • Mounting Facility Type And Quantity

    2 threaded hole

  • Thread Quantity Per Inch

    32

  • Body Width

    0.740 inches minimum and 0.760 inches maximum

  • Circuit Protection Type

    overcurrent single location

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac single location

  • Inclosure Protection Type For Which Designed

    fungus resistant and moisture resistant

  • Pole Quantity

    1

  • Manual Actuator Type And Quantity

    1 toggle

  • Internal Trip Release Configuration

    series trip single location

  • Nominal Thread Size

    0.138 inches

  • Trip Release Characteristic

    time delay single location

  • Main Contact Tripping Mechanism Type

    trip free

  • Arc Quenching Method

    magnetic blowout

  • Frequency In Hertz

    400.0 single location

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.052 inches minimum and 2.072 inches maximum

  • Body Style

    single pole type

  • Trip Release Method

    magnetic-hydraulic single location

  • Body Length

    2.490 inches minimum and 2.510 inches maximum

  • Ultimate Trip Time Per Pole In Seconds

    9.000 minimum single location

  • Boss Height

    0.130 inches minimum and 0.150 inches maximum

  • Case Material

    plastic

  • Terminal Type And Quantity

    2 threaded stud

  • Fragility Factor

    moderately rugged

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    130.0 single location

  • Thread Series Designator

    unc

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac single location

  • Reset Method

    manual

  • Trip Delay Time In Seconds Per Rated Continuous Current

    2.000 minimum at 200 pct single location and 3.000 maximum at 400 pct single location and 0.800 minimum at 300 pct single location and 6.000 maximum at 300 pct single location and 0.400 minimum at 400 pct single location and 20.000 maximum at 200 pct

  • Mounting Surface To Terminal End Distance

    2.461 inches minimum and 2.481 inches maximum

  • ~1

    single location and 0.100 minimum at 500 pct sing

Related Manufacturers

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...