NSN: 5925-01-065-5510
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Bushing Length
0.280 inches minimum and 0.380 inches maximum
-
Body Width
1.562 inches maximum
-
Case Material
metal
-
Center To Center Distance Between Terminals Parallel To Length
0.625 inches nominal
-
Mounting Facility Type And Quantity
1 threaded bushing
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
3.0 amperes ac
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac
-
Trip Release Method
magnetic
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Ultimate Trip Time Per Pole In Seconds
0.100 nominal
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Internal Trip Release Configuration
series trip
-
Nominal Thread Size
0.375 inches
-
Inclosure Protection Type For Which Designed
fungus resistant
-
Special Features
2 6-32unc-2b holes on 1.374 cente rs located on front of breaker
-
Frequency In Hertz
400.0
-
Thread Series Designator
unef
-
Body Length
1.937 inches maximum
-
Center To Center Distance Between Terminals Parallel To Width
0.906 inches maximum
-
Mounting Surface To Terminal End Distance
1.828 inches maximum
-
Pole Quantity
3
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
300.0 ac
-
Circuit Protection Type
overcurrent
-
Trip Release Characteristic
time delay
-
Reset Method
manual
-
Actuator Function
trip-reset
-
Actuator Position Designation
at pole two
-
Trip Delay Time In Seconds Per Rated Continuous Current
3600.000 nominal at 100 pct and 3.000 minimum at 125 pct and 60.000 maximum at 125 pct and 0.500 minimum at 200 pct and 9.000 maximum at 200 pct and 0.000 minimum at 400 pct and 1.750 maximum at 400 pct
-
Terminal Type And Quantity
6 wire hook
-
Departure From Cited Designator
as modified by features