NSN: 5925-01-086-5643
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
~1
locations
-
Center To Center Distance Between Terminals Parallel To Length
0.469 inches minimum and 0.531 inches maximum
-
Thread Series Designator
uns
-
Body Width
0.730 inches minimum and 0.770 inches maximum
-
Case Material
plastic
-
Trip Release Method
thermal all locations
-
Trip Release Ambient Temp Rating
25.0 deg celsius maximum all locations
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Reset Method
manual
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
145.0 all locations
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Internal Trip Release Configuration
series trip all locations
-
Mounting Facility Type And Quantity
thd bushing
-
Thread Quantity Per Inch
32
-
Nominal Thread Size
0.438 inches
-
Maximum Continuous Load Current Rating Per Pole
7.5 amperes ac all locations
-
Manual Actuator Type And Quantity
1 push-pull
-
Actuator Position Designation
at pole two
-
Body Style
multipole-single actuator type
-
Body Height
1.319 inches minimum and 1.381 inches maximum
-
Main Contact Tripping Mechanism Type
trip free
-
Terminal Type And Quantity
6 screw
-
Body Length
1.840 inches maximum
-
Bushing Length
0.219 inches minimum and 0.281 inches maximum
-
Frequency In Hertz
400.0 all locations
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
2000.0 ac all locations
-
Center To Center Distance Between Terminals Parallel To Width
0.593 inches minimum and 0.655 inches maximum
-
Trip Delay Time In Seconds Per Rated Continuous Current
20.000 maximum at 200 pct all locations and 2.000 maximum at 500 pct all locations and 0.100 minimum at 1000 pct all locations and 4.000 minimum at 200 pct all locations and 0.400 minimum at 500 pct all locations and 0.530 maximum at 1000 pct all