NSN: 5925-01-094-3466
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Actuator Function
trip-reset
-
Storage Type
general purpose warehouse
-
Reset Method
manual
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
3
-
Terminal Type And Quantity
6 threaded stud
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
10.875 inches nominal
-
Case Material
plastic
-
Operating Voltage Type And Rating Per Pole In Volts
500.0 ac all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
60.000 maximum at 200 pct all locations
-
Center To Center Distance Between Terminals Parallel To Length
10.875 inches nominal
-
Body Width
8.000 inches nominal
-
Mounting Surface To Terminal End Distance
9.031 inches nominal
-
Body Length
12.000 inches nominal
-
Special Features
shunt trip 120vdc
-
Maximum Continuous Load Current Rating Per Pole
150.0 amperes ac all locations
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Main Contact Tripping Mechanism Type
trip free
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
100000.0 ac all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
3.000 inches nominal
-
Adjustable Trip Setting Current Range Per Pole In Amps
+650.0/+1300.0 ac all locations
-
Frequency In Hertz
60.0 all locations
-
Manual Actuator Type And Quantity
1 toggle
-
Boss Height
0.250 inches nominal
-
Body Style
multipole-single actuator type
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
-
Inclosure Protection Type For Which Designed
fungus resistant
-
Actuator Position Designation
at pole two
-
Trip Release Method
thermal-magnetic all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Center To Center Distance Between Terminals Parallel To Width
3.000 inches nominal
-
Unthreaded Mounting Hole Diameter
0.250 inches nominal
-
Features Provided
adjustable trip release and high inrush protection