NSN: 5925-01-096-3090
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Style
8c multipole-multiple actuator type
-
Case Material
plastic
-
Fragility Factor
moderately rugged
-
Pole Quantity
2
-
Arc Quenching Method
magnetic blowout
-
Storage Type
general purpose warehouse
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes dc all locations
-
Trip Release Method
magnetic-hydraulic all locations
-
Trip Release Characteristic
time delay all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
2 toggle
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip all locations
-
Nominal Thread Size
0.138 inches
-
Inclosure Protection Type For Which Designed
fungus resistant
-
Thread Series Designator
unc
-
Terminal Type And Quantity
4 tab, solder lug
-
Body Length
1.968 inches minimum and 2.032 inches maximum
-
Body Width
1.468 inches minimum and 1.532 inches maximum
-
Center To Center Distance Between Terminals Parallel To Length
1.528 inches minimum and 1.592 inches maximum
-
Center To Center Distance Between Terminals Parallel To Width
0.718 inches minimum and 0.782 inches maximum
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.628 inches minimum and 1.692 inches maximum
-
Switch Contact Arrangement
single pole, double throw
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.718 inches minimum and 0.782 inches maximum
-
Boss Height
0.098 inches minimum and 0.162 inches maximum
-
Mounting Surface To Terminal End Distance
1.918 inches minimum and 1.950 inches maximum
-
Mounting Facility Type And Quantity
4 threaded hole
-
Operating Voltage Type And Rating Per Pole In Volts
65.0 dc all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 dc all locations
-
Circuit Protection Type
overcurrent all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Ultimate Trip Time Per Pole In Seconds
60.000 maximum all locations
-
Reset Method
manual
-
Actuator Position Designation
at each pole
-
External Actuator Linkage Arrangement
one and two linked
-
Auxiliary Switch Function And Quantity
1 alarm
-
Switch Location And Position Designation
external at pole one
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.800 minimum at 200 pct all locations and 12.000 maximum at 200 pct
-
Switch Terminal Type
tab, solder lug
-
Switch Current Rating And Type In Amps
10.0 ac
-
Switch Voltage Rating And Type In Volts
250.0 ac
-
Unpackaged Unit Weight
5.000 ounces