NSN: 5925-01-098-9980
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal .
-
Frequency In Hertz
400.0
-
Thread Series Designator
unf
-
Body Style
caaql 1a
-
Body Length
1.375 inches nominal
-
Body Width
0.690 inches nominal
-
Case Material
plastic
-
Mounting Facility Type And Quantity
1 threaded bushing
-
Storage Type
general purpose warehouse
-
Thread Quantity Per Inch
24
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac and 1000.0 dc .
-
Circuit Protection Type
overcurrent .
-
Trip Release Method
thermal .
-
Trip Release Characteristic
time delay .
-
Nominal Thread Size
0.375 inches
-
Trip Delay Time In Seconds Per Rated Continuous Current
6.000 minimum at 200 pct and 20.000 maximum at 200 pct .
-
Terminal Type And Quantity
2 tab w/screw
-
Bushing Length
0.375 inches nominal
-
Center To Center Distance Between Terminals Parallel To Length
1.020 inches nominal
-
Fragility Factor
moderately rugged
-
Mounting Surface To Terminal End Distance
2.035 inches nominal
-
Pole Quantity
1
-
Arc Quenching Method
air
-
Maximum Continuous Load Current Rating Per Pole
60.0 amperes ac and 60.0 amperes dc .
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac and 50.0 dc .
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
135.0
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 push-pull
-
Actuator Function
trip-reset
-
Actuator Position Designation
at pole one
-
Internal Trip Release Configuration
series trip .
-
Inclosure Protection Type For Which Designed
humidity resistant and salt spray proof and shock resistant and vibration resistant