NSN: 5925-01-101-9481
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Height
1.811 inches minimum and 1.875 inches maximum
-
Actuator Position Designation
at each pole
-
Arc Quenching Method
magnetic blowout
-
Mounting Facility Type And Quantity
4 clip
-
Maximum Continuous Load Current Rating Per Pole
5.0 amperes ac all locations
-
Circuit Protection Type
overcurrent all locations
-
Trip Release Method
magnetic-hydraulic all locations
-
Trip Release Characteristic
time delay all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
2 toggle
-
External Actuator Linkage Arrangement
one and two linked
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Unpackaged Unit Weight
5.000 ounces
-
Terminal Type And Quantity
4 quick disconnect, male
-
Body Width
1.718 inches minimum and 1.782 inches maximum
-
Center To Center Distance Between Terminals Parallel To Width
0.923 inches minimum and 0.987 inches maximum
-
Boss Height
0.093 inches minimum and 0.157 inches maximum
-
Pole Quantity
2
-
Storage Type
general purpose warehouse
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac all locations
-
Actuator Function
trip-reset
-
Body Style
6c multipole-multiple actuator type
-
Body Length
2.418 inches minimum and 2.482 inches maximum
-
Case Material
plastic
-
Fragility Factor
moderately rugged
-
Internal Trip Release Configuration
series trip all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.500 minimum at 200 pct and 1.500 maximum at 200 pct all locations
-
Frequency In Hertz
400.0