NSN: 5925-01-103-8319
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Length
1.531 inches minimum and 1.562 inches maximum
-
Case Material
metal
-
Center To Center Distance Between Terminals Parallel To Length
0.875 inches minimum and 0.906 inches maximum
-
Storage Type
general purpose warehouse
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
9.0 amperes ac and 9.0 amperes dc
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
300.0 ac and 500.0 dc
-
Trip Release Method
magnetic
-
Thread Series Designator
unef
-
Terminal Type And Quantity
2 wire hook
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.500 minimum at 200 pct and 9.000 maximum at 200 pct
-
Internal Trip Release Configuration
series trip
-
Actuator Position Designation
at pole one
-
Manual Actuator Type And Quantity
1 toggle
-
Main Contact Tripping Mechanism Type
trip free
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Specification/Standard Data
81349-mil-c-39019/1 government specification
-
Body Style
single pole type
-
Bushing Length
0.332 inches minimum and 0.380 inches maximum
-
Body Width
0.594 inches minimum and 0.625 inches maximum
-
Mounting Surface To Terminal End Distance
1.669 inches minimum and 1.700 inches maximum
-
Pole Quantity
1
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac and 50.0 dc
-
Circuit Protection Type
overcurrent
-
Trip Release Characteristic
time delay
-
Reset Method
manual
-
Actuator Function
trip-reset
-
Nominal Thread Size
0.375 inches
-
Inclosure Protection Type For Which Designed
hermetically sealed
-
Frequency In Hertz
400.0
-
Test Data Document
81349-mil-c-39019 specification