NSN: 5925-01-107-6622

Circuit Breakers

CIRCUIT BREAKER

5925 - Circuit Breakers

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Test Data Document

    81349-mil-c-55629 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type

  • Main Contact Tripping Mechanism Type

    trip free

  • Arc Quenching Method

    magnetic blowout

  • Center To Center Distance Between Terminals Parallel To Length

    1.529 inches minimum and 1.591 inches maximum

  • Maximum Continuous Load Current Rating Per Pole

    30.0 amperes ac all locations

  • Bushing Length

    0.099 inches minimum and 0.161 inches maximum

  • Frequency In Hertz

    400.0 all locations

  • Trip Delay Time In Seconds Per Rated Continuous Current

    2.100 minimum at 200 pct all locations and 20.000 maximum at 200 pct all locations

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.629 inches minimum and 1.691 inches maximum

  • Auxiliary Switch Function And Quantity

    1 alarm

  • Terminal Type And Quantity

    6 tab w/screw

  • Specification/Standard Data

    81349-mil-c-55629/12 government specification

  • Manual Actuator Type And Quantity

    3 toggle

  • Switch Voltage Rating And Type In Volts

    240.0 ac and 50.0 dc

  • Switch Location And Position Designation

    internal at pole one

  • Case Material

    plastic

  • Nominal Thread Size

    0.138 inches

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    150.0 all locations

  • Mounting Facility Type And Quantity

    6 threaded hole

  • Switch Contact Arrangement

    single pole, double throw

  • Body Length

    2.219 inches minimum and 2.281 inches maximum

  • Inclosure Protection Type For Which Designed

    fungus resistant

  • Body Style

    multipole-multiple actuator type

  • Trip Release Method

    magnetic all locations

  • Body Width

    1.969 inches minimum and 2.031 inches maximum

  • Operating Voltage Type And Rating Per Pole In Volts

    240.0 ac all locations

  • Thread Quantity Per Inch

    32

  • Mounting Surface To Terminal End Distance

    2.032 inches maximum

  • Center To Center Distance Between Terminals Parallel To Width

    1.629 inches minimum and 1.691 inches maximum

  • Switch Current Rating And Type In Amps

    5.0 ac and 5.0 dc

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations

  • Internal Trip Release Configuration

    series trip all locations

  • External Actuator Linkage Arrangement

    one, two, and three linked

  • Actuator Function

    trip-reset

  • Trip Release Characteristic

    time delay all locations

  • Storage Type

    general purpose warehouse

  • Reset Method

    manual

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    0.719 inches minimum and 0.781 inches maximum

  • Actuator Position Designation

    at each pole

  • Thread Series Designator

    unc

  • Circuit Protection Type

    overcurrent all locations

  • Pole Quantity

    3

  • ~1

    data on certain environmental and performanc

  • Special Handling Feature

    magnetic

  • Switch Terminal Type

    tab, solder lug

  • Fragility Factor

    moderately rugged

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...