NSN: 5925-01-111-4508
Circuit Breakers
CIRCUIT BREAKER
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Case Material
plastic
-
Mounting Facility Type And Quantity
2 clip
-
Circuit Protection Type
overcurrent all locations
-
Internal Trip Release Configuration
relay trip second location
-
Pole Quantity
2
-
Reset Method
manual
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.050 maximum at 200 pct second location and 0.025 maximum at 300 pct second location
-
Trip Release Characteristic
time delay all locations
-
Center To Center Distance Between Terminals Parallel To Width
0.625 inches nominal
-
Actuator Function
trip-reset
-
Body Length
2.000 inches nominal
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations and 1000.0 dc all locations
-
Body Height
1.555 inches maximum
-
Trip Release Method
magnetic-hydraulic all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Internal Trip Release Configuration
series trip first location
-
Inclosure Protection Type For Which Designed
fungus resistant
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac first location
-
Body Style
multipole-single actuator type
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Position Designation
between pole one and two
-
Main Contact Tripping Mechanism Type
trip free
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.500 minimum at 200 pct first location and 9.000 maximum at 200 pct first location
-
Boss Height
0.125 inches nominal
-
Body Width
1.540 inches nominal
-
Terminal Type And Quantity
6 quick disconnect, male
-
Frequency In Hertz
50.0 first location or 60.0 first location
-
Operating Voltage Type And Rating Per Pole In Volts
24.0 dc second location